NEGAbriefLocal records made useful
IssueFranklin Countyunder consideration

Georgia EPD draft permit proposes 30-day NOx limit for combustion turbine and duct burner stacks

A draft state air permit would set a rolling emission standard and required pollution controls for the facility's combustion turbines, limits that affect how much nitrogen oxide the plant can release.

By NEGA Brief NewsroomLast checked September 30, 2026
What happens next

No next step has been documented.

The story

Georgia's Environmental Protection Division has drafted a permit condition setting a 30-day rolling average NOx emission standard of 15 ppmvd, corrected to 15% oxygen, when the unit is operating at or above 256 MW.

SourcesTV-938555 draft

The same draft would require best available control technology for NOx on the combustion turbines and duct burners, including dry low NOx combustors, low NOx burners, and selective catalytic reduction add-on control equipment.

SourcesTV-938555 draft

What happened

How this issue got here

Open any step for its supporting record. A proposal remains labeled as proposed until later evidence establishes an outcome.

Appeared on agenda
proposed

NOx emission standards for combined-cycle combustion turbines and duct burners (30-day rolling average)

15 ppmvd, corrected to 15% oxygen, when operating at or above 256 MW

Appeared on agenda
proposed

Required Best Available Control Technology (BACT) for NOx: dry low NOx combustors, low NOx burners, and selective catalytic reduction on combustion turbines and duct burners

selective catalytic reduction add-on control equipment